ITC VA-6200MS 500W 8 Zones EVAC Extension Controller, 8 zones and A+B independent dual speaker loop output, 6 general audio inputs and 1 MP3 input, Output Voltage: 100V, MIC1-2 Input Distortion: <1% (output rating), 1KHz, MIC1-2 Input Frequency Response: 80Hz~20KHz, MIC1-2 Input Sensitivity: 5mV/6/600Ω, MIC1-2 Input SNR: >65dB, AUX3-6 Input Distortion: <1% (output rating), 1KHz, AUX3-6 Input Frequency Response: 80Hz~20KHz, AUX3-6 Input Sensitivity: 350mV/10kΩ, AUX3-6 Input SNR: >70dB, Spare Amplifier Input: 100V, Spare Amplifier Audio Signal Output: ±385mV (balanced output), Alarm Input: 8, Alarm Output: 8, Zone Input: 8, 24V Relay Output: 8, Fuse Size: 250V/5A.

https://www.esco.pk/web/image/product.template/24531/image_1920?unique=003a51d

    Rs. 0.00 0.0 PKR Rs. 0.00

    Not Available For Sale

    This combination does not exist.

    Add to wishlist Compare

    Please get in touch for pricing & availability.

    Is our price higher than expected or showing as zero? Chat with us now for the best price and product availability. Prices if shown are inclusive of applicable taxes. Tax rate may be adjusted as per customer's taxation status. For supply of product only, excluding any cabling and/or installation. Shipping charges can sometimes vary.


    Features:

    * Built-in 500W amplifier, with 8 zones and A+B independent dual speaker loop output, each zone has independent LED indicator light, output control button and volume adjustment.

    * Audio processing with 6 general audio inputs and 1 MP3 input, it can connect with external microphone, CD player, tuner and etc, it can play any audio source in any zone. Among them, 2 channels have 24V phantom power microphone input, 4 channels are AUX input and 1 channel is MP3 audio channel from the controller.

    * With fault self-check of power-on system, and fault full check of manual system function.

    * With real-time indication of system status.

    * Connecting with one backup amplifier, when built-in amplifier damaged, it will switch to backup amplifier automatically.

    * Automatically monitor every zone speaker loop status (open circuit, short circuit) in real-time.

    * 8-channel short-circuit/level trigger mode, the trigger response can be configured with 3 different channels of EVAC, ALERT, and LINE3, and the output can be arbitrarily configured with partition, group, and short-circuit contact combination.

    * Support external 24V backup power supply, realize power-off continuous normal operation without delay;

    * Extension port can connect controller and next extension device.

    * The partition output has three-wire and four-wire forced-cut adjustment functions

    Specifications:

    Rated Power Output

    500W

    Output Voltage

    100V

    MIC1-2 Input Distortion

    <1% (output rating), 1KHz

    MIC1-2 Input Frequency Response

    80Hz~20KHz

    MIC1-2 Input Sensitivity

    5mV/6/600Ω

    MIC1-2 Input SNR

    >65dB

    AUX3-6 Input Distortion

    <1% (output rating), 1KHz

    AUX3-6 Input Frequency Response

    80Hz~20KHz

    AUX3-6 Input Sensitivity

    350mV/10kΩ

    AUX3-6 Input SNR

    >70dB

    Spare Amplifier Input

    100V

    Spare Amplifier Audio Signal Output

    ±385mV (balanced output)

    Alarm Input

    8

    Alarm Output

    8

    Zone Input

    8

    24V Relay Output

    8

    Short Circuit mode

    short circuit

    Type of cooling

    air-cooled

    Guard mode

    delay/overheat/ short circuit/ overload

    Output Volume Control

    6

    Supply Voltage

    ~ 220V-240V, 50/60Hz

    Maximum Current

    3A

    Fuse Size

    250V/5A, slow type

    Spare Voltage

    24V DC, ±20%

    Maximum Current

    30A

    Maximum Power Consumption

    600W

    Dimensions (L x W x D)

    484 x 88 x 353mm

    Weight

    10.5kg

    Installation method

    Desktop or 19" cabinet