Skip to Content
LBB1990/00 LBB1990/00 Request a Quote

LBB1990/00

The Bosch LBB1990/00 is the main controller for the PLENA Voice Alarm System. It routes live announcements and prerecorded evacuation messages to selected loudspeaker zones and monitors the loudspeaker lines for faults.

Rs. 0 Rs. 0

  • Brand - BOSCH
BOSCH
BOSCH

Global leader in Public Address, Voice Evacuation and Conference Systems.

Bosch PLENA voice alarm rack in a building lobby with people on a staircase Bosch, Invented for life

The fast route to safety

PLENA Public Address and Voice Alarm System

LBB1990/00

PLENA voice alarm components

LBB1990/00 PLENA Voice Alarm Controller

Heart of the PLENA Voice Alarm System: six zones on board, up to 120 with routers, a built-in 240 W amplifier and message manager, supervised emergency microphone.

  • 6 Zones up to 120
  • 240 W Amplifier Built In
  • EN 54-16 Certified
  1. LBB1990/00 Controller
  2. LBB1992/00 Router
  3. LBB193x/xx Amplifiers
  4. LBB1956/00 Call Station
  5. LBB1957/00 Keypad
  6. LBB1995/00 Fireman's Panel · ask us

BOSCH · PLENA VOICE ALARM

Bosch LBB1990/00 Capabilities

The EN 54-16-certified Bosch LBB1990/00 is the central controller for evacuation announcements, everyday paging and background music in a PLENA Voice Alarm System.

  • Emergency Paging & Supervision

    Give live evacuation instructions with the supervised emergency microphone. The front panel provides zone selection, all-call and alert controls, plus 13 LEDs for system faults. Loudspeaker line impedance monitoring helps detect wiring faults.

  • Built-in Message Manager

    Store up to 255 WAV messages in 16 MB of non-volatile flash memory. Combine recordings into a single announcement for alerts, evacuation instructions or routine paging.

  • 100 V Zone Outputs & Expansion

    Route announcements through six transformer-isolated 100 V zone outputs. Expand to 120 zones with PLENA routers and connect up to eight call stations.

  • 240 W Built-in Amplifier

    The built-in 240 W RMS amplifier powers emergency calls and background music. Add an external amplifier for two-channel operation so music can continue in zones that are not receiving a call.

  • Programmable Triggers & Priorities

    Assign messages and zones to six emergency and six business trigger inputs. The controller supports 16 priority levels and six volume-override outputs for priority announcements.

  • Background Music & Audio Inputs

    Connect two background music sources and set music levels by zone. Adjust bass and treble from the front panel. The separate mic/line input supports configurable priority, a speech filter, phantom power and selectable VOX.

BOSCH · PLENA VOICE ALARM

Where the Bosch LBB1990/00 Is Used

Select a setting to see how the LBB1990/00 handles paging, voice alarms and audio distribution in Bosch’s PLENA examples.

Choose a PLENA application
Sunlit classroom with light-wood desks, navy chairs and a blank whiteboard
Illustrative image

BOSCH CONFIGURATION EXAMPLE

Schools

Office staff can page selected classrooms or shared areas. School chimes and emergency announcements can use the same PLENA system.

Loudspeaker zones
30
Six-zone routers
4
Indoor community lap pool with blue lane ropes and tall windows
Illustrative image

BOSCH CONFIGURATION EXAMPLE

Indoor Swimming Pools

Reception can make announcements for separate areas such as the main pool, children's pool and changing rooms.

Loudspeaker zones
5
Six-zone routers
0
Skylit shopping mall atrium with central escalators and glass railings
Illustrative image

BOSCH CONFIGURATION EXAMPLE

Shopping Malls

A security control room can page individual areas across the mall. Public areas can carry background music during normal operation.

Loudspeaker zones
54
Six-zone routers
8
Hotel lobby with a stone-and-timber reception desk and navy guest seating
Illustrative image

BOSCH CONFIGURATION EXAMPLE

Hotels

Reception and office staff can page selected areas. The same system can provide background music in spaces such as the lobby and restaurant.

Loudspeaker zones
12
Six-zone routers
1
bosch-lbb1990-00-eu-declaration-of-conformity.pdf
Download
bosch-lbb1990-00-voice-alarm-controller-datasheet.pdf
Download
bosch-plena-vas-configuration-software-manual-2-16-04-r2.pdf
Download
bosch-public-address-portfolio-brochure.pdf
Download

Key specs

  • 6 zones on board, up to 120 with LBB1992/00 routers
  • Built-in 240 W amplifier, 100 V outputs, A/B wiring
  • Message manager, up to 255 messages
  • 6 emergency and 6 business triggers, 16 priorities
  • Up to 8 call stations on CAT-5
  • Supervised emergency microphone and loudspeaker lines
  • EN 54-16 / ISO 7240-16 certified, 2 U
Chat on WhatsApp

Bosch LBB1990/00 Technical Specifications

System

SpecificationValue
Loudspeaker zones6 onboard, expandable to 120 with additional six-zone routers
Supported call stationsUp to 8
Priority levels16
System supervisionLoudspeaker line impedance, emergency microphone, message manager, and amplifiers
Loudspeaker wiringA/B wiring supported

Electrical

SpecificationValue
Mains supply230/115 V AC, ±15%, 50/60 Hz
Mains inrush current8 A
Maximum apparent power600 VA
Battery backup supply24 V DC, ±15%
Maximum battery supply current14 A

Amplifier and Audio Performance

SpecificationValue
Built-in amplifier output240 W RMS / 360 W maximum
Output reduction on backup power−1 dB
Frequency response60 Hz to 18 kHz (+1/−3 dB at −10 dB relative to rated output)
Distortion<1% at rated output, 1 kHz
Bass adjustment±8 dB at 100 Hz
Treble adjustment±8 dB at 10 kHz

Audio Inputs

SpecificationValue
Mic/line input1 × input with XLR and 6.3 mm jack
Mic/line sensitivity1 mV mic / 1 V line
Mic/line impedance>1 kΩ mic / >5 kΩ line
Mic/line signal-to-noise ratio>63 dB mic / >70 dB line at maximum volume. >75 dB at minimum volume or muted.
Mic/line common-mode rejection>40 dB (50 Hz to 20 kHz)
Mic/line headroom>25 dB
Speech filterHigh-pass, −3 dB at 315 Hz, 6 dB/octave
Phantom power12 V in microphone mode
VOX trigger level−20 dB (100 µV mic / 100 mV line), or activation via input contact
LimiterAutomatic
Background music inputs2 × unbalanced RCA inputs, stereo summed to mono
RCA line input sensitivity / impedance200 mV / 22 kΩ
RCA line input signal-to-noise ratio>70 dB at maximum volume. >75 dB at minimum volume or muted.
RCA line input headroom>25 dB
100 V inputMSTB 2.5/16-ST connector, 1,000 W power handling

Audio Outputs

SpecificationValue
Loudspeaker outputsSix transformer-isolated 100 V zones with floating MSTB 2.5/16-ST connections
Zone output rating700 W per zone output
Separate amplifier output70 V and 100 V
Call-only output100 V
Tape output1 × RCA pair (2 × mono), 350 mV nominal, <1 kΩ
Background music attenuation per zone0 / −3 / −6 / −9 / −12 / −15 dB
Corresponding background music output voltage70 / 50 / 35 / 25 / 18 / 13 V

Control and Connectivity

SpecificationValue
Trigger inputs12 programmable inputs, split into 6 emergency and 6 business inputs
Trigger input connectorMC 1.5/14-ST-3.5
Emergency input supervisionProgrammable, using series/parallel resistors
Volume override outputs6 configurable outputs supporting 3-wire, 4-wire (24 V), and fail-safe 4-wire connections
Relay contact rating100 V, 2 A, voltage-free
Relay connectorMC 1.5/14-ST-3.5
Emergency and call active relaysNO / COM / NC
Fault relayNO / COM / NC, normally energized for fail-safe operation
General-purpose relaysNO / COM
System interconnectionsRJ45 over shielded CAT-5
Call station and remote-control connectionsTwo redundant connectors for each
Router connectionLBB1992/00 PLENA Voice Alarm Router
PC configuration and message uploadUSB 2

Message Manager

SpecificationValue
Audio file formatMono WAV, 16-bit PCM
Supported sample rates24 / 22.05 / 16 / 12 / 11.025 / 8 kHz
Frequency response at 24 kHz100 Hz to 11 kHz (+1/−3 dB)
Frequency response at 22.05 kHz100 Hz to 10 kHz (+1/−3 dB)
Frequency response at 16 kHz100 Hz to 7.3 kHz (+1/−3 dB)
Frequency response at 12 kHz100 Hz to 5.5 kHz (+1/−3 dB)
Frequency response at 11.025 kHz100 Hz to 5 kHz (+1/−3 dB)
Frequency response at 8 kHz100 Hz to 3.6 kHz (+1/−3 dB)
Distortion<0.1% at 1 kHz
Signal-to-noise ratio>80 dB at maximum volume
Internal memory16 MB flash ROM
Maximum stored messages255
Recording and playback time1,000 s at 8 kHz or 333 s at 24 kHz
Flash memory supervisionContinuous checksum verification
DAC supervision1 Hz pilot tone
Data retention>10 years

Power Consumption

SpecificationValue
Mains operation, maximum550 W
Mains operation at −3 dB / −6 dB440 W / 340 W
Mains operation with pilot tone / idle136 W / 60 W
24 V DC operation, maximum14.0 A (336 W)
24 V DC operation at −3 dB / −6 dB12.5 A (300 W) / 9.5 A (228 W)
24 V DC operation with pilot tone / idle2.5 A (60 W) / 0.9 A (22 W)
Pilot-tone test condition20 kHz at −20 dB with maximum loudspeaker load

Mechanical

SpecificationValue
Dimensions (H × W × D)144 × 430 × 370 mm
Rack mounting19-inch rack, 3U
WeightApprox. 21.17 kg
ColourCharcoal

Environmental

SpecificationValue
Operating temperature−10 °C to +55 °C (+14 °F to +131 °F)
Storage and transport temperature−40 °C to +70 °C (−40 °F to +158 °F)
Relative humidity<95%
Fan noise<48 dB SPL at 1 m at maximum output

Standards

SpecificationValue
Voice alarm certificationEN 54-16
SafetyEN 60065
ImmunityEN 50130-4
EmissionsEN 55103-1
Questions & answers

Know before you buy

Quick answers about the LBB1990/00, and how it compares.

What is the Bosch LBB1990/00?
The Bosch LBB1990/00 is the main controller for the PLENA Voice Alarm System. It routes live announcements, prerecorded evacuation messages, and background music to selected loudspeaker zones. It also monitors loudspeaker lines for faults.
How many loudspeaker zones can the Bosch LBB1990/00 control?

The controller supports six zones on its own. A PLENA Voice Alarm System can expand to up to 120 zones using Bosch LBB1992/00 six-zone routers.

Which loudspeakers are compatible with the Bosch LBB1990/00?
The controller’s six zone outputs are designed for 100 V constant-voltage loudspeakers. For voice alarm projects, select compatible voice alarm loudspeakers and verify the total loudspeaker load as part of the system design.
Can the voice alarm controller keep working during a power outage?
Yes. The LBB1990/00 has a 24 V DC input for an external backup power supply that powers the system when mains power is unavailable. Backup runtime depends on the connected supply and the system load.
Can a fire alarm panel trigger a prerecorded evacuation message?
Yes. A compatible contact output from the fire alarm panel can activate one of the controller’s six programmable emergency inputs. The PLENA configuration assigns the message and loudspeaker zones to that input.
Does the Bosch LBB1990/00 need an external amplifier?
The Bosch LBB1990/00 has a built-in 240 W RMS amplifier that can drive 100 V loudspeakers within its rated load. An external amplifier can be added for two-channel operation, allowing announcements in selected zones while background music continues in other zones.
Who is the authorized Bosch distributor in Pakistan?
ESCO (Electronic Security Company) is an authorized Bosch distributor in Pakistan. Contact ESCO to check the current Bosch LBB1990/00 price and availability or request a project quotation.
Accessory Products
Chat on WhatsApp
WhatsApp