Skip to Content
LBB1938/30 LBB1938/30 Request a Quote

LBB1938/30

The Bosch LBB1938/30 is the 480 W power amplifier of the PLENA Voice Alarm System: 70 V / 100 V and 8 ohm outputs, dual inputs with priority switching, EN 54-16 certified, 3 U. Scroll down for details.

Rs. 0 Rs. 0

  • Brand - BOSCH
BOSCH
BOSCH

Global leader in Public Address, Voice Evacuation and Conference Systems.

Bosch PLENA voice alarm rack in a building lobby with people on a staircase Bosch, Invented for life

The fast route to safety

PLENA Public Address and Voice Alarm System

LBB1938/30

PLENA voice alarm components

LBB1938/30 PLENA 480 W Power Amplifier

480 W amplifier for the PLENA Voice Alarm System: 70 V / 100 V and 8 ohm outputs, dual inputs with priority switching, EN 54-16 certified.

  • 480 W Output
  • 70 V / 100 V and 8 Ohm
  • EN 54-16 Certified
  1. LBB1990/00 Controller
  2. LBB1992/00 Router
  3. LBB193x/xx Amplifiers
  4. LBB1956/00 Call Station
  5. LBB1957/00 Keypad
  6. LBB1995/00 Fireman's Panel · ask us

Power Amplifier

Bosch LBB1938/30 480W Plena Power Amplifier

Performance

50 Hz to 20 kHz (+1/‑3 dB @ ‑10 dB ref. rated output)

<1% @ rated output power, 1 kHz

Loudspeaker Output

The amplifier has 70 V and 100 V outputs for constant voltage loudspeaker systems and a low impedance output for 8 Ohm loudspeaker loads.

Priority Controlled Output

The LBB 1938/30 has two separate priority controlled 100 V outputs for zones that only need announcements made via the priority input, and for zones that will not get any announcements made via the priority input.

Line Inputs

Dual inputs with priority switching

Line Loop-through

The system has two balanced inputs with priority control, each with a loop-through facility. This makes it easy to connect remote systems that require priority control. 

Controls and Indicators

Overheat indicator, Air inlet for forced air cooling, Battery operation indicator

Level control input 1 & 2, Power button, Mains switch

Protection

The amplifier is protected against overload and short circuits. A temperature-controlled fan ensures high reliability at high output levels and low acoustic noise at lower output levels.

Key specs

  • 480 W output power
  • 70 V / 100 V and 8 ohm outputs
  • Dual inputs with priority switching, 100 V slave input
  • EN 54-16 / ISO 7240-16 certified
  • 3 U 19" housing

Electrical

Mains Power Supply

­Voltage

230 VAC ±10%, 50/60 Hz

Inrush current

19 A

Max power consumption

2200 VA

Battery Power Supply

Voltage

24 VDC +15% / -15%

Current max

30 A

Performance

Output power (rms/maximum)

480 / 720 W

Power reduction on backup power

-1 dB

Frequency response

50 Hz to 20 kHz (+1 / -3 dB at -10 dB ref. rated output)

Distortion

<1% at rated output power, 1 kHz

S/N (flat at max volume)

>90 dB

Line inputs

2 x

Connector

3-pin XLR, balanced

Sensitivity

1 V

Impedance

20 kohm

CMRR

>25 dB (50 Hz to 20 kHz)

Gain

40 dB

100 V Input

Connector

Screw, unbalanced

Sensitivity

100 V

Impedance

330 kohm

Line loop-through output

2 x

Connector

3-pin XLR

Nominal level

1 V

Impedance

Direct connection to line input

Loudspeaker Outputs

3 x

Connector

Screw, floating

Direct output

100 V, 70 V, 8 ohm

Priority only (from input 1)

100 V or 70 V internally selectable

Music (non-priority) only

100 V or 70 V internally selectable

Power Consumption

Mains operation

Max power

990 W

-3dB

715 W

-6dB

510 W

Pilot tone

110 W

Idle

125 W

24 VDC operation

Max power

32 A (770 W)

-3 dB

26 A (625 W)

-6 dB

18 A (430 W)

Pilot tone*

3.8 A (91 W )

Idle

0.7 A (17 W)

Mechanical

Dimensions (H x W x D)

145 x 430 x 370 mm (19" wide, 3U high, with feet)

Weight

Approx. 25 kg

Mounting

Standalone, 19”rack

Color

Charcoal

Environmental

Operating temperature

-10 ºC to +55 ºC (14 ºF to +131 ºF)

Storage temperature

-40 ºC to +70 ºC (-40 ºF to +158 ºF)

Relative humidity

<95%

Acoustic noise level of fan

<48 dB SPL at 1 m (max output)